Sign In | Join Free | My xuijs.com |
|
Categories | Transformer Testing Equipment |
---|---|
Brand Name: | Delta |
Model Number: | TTR-Z |
Certification: | ISO9001 |
Place of Origin: | China |
MOQ: | 1 set Turns Ratio Testing Equipment |
Price: | USD1.0 |
Payment Terms: | T/T, Western Union |
Supply Ability: | 1000 sets per month |
Delivery Time: | 10 days |
Packaging Details: | Turns Ratio Testing Equipment packed in veneer case |
Item Name: | TTR-Z Special Z Type Transformer Turns Ratio Testing Equipment |
Functions: | Test the turns ratio and group vector of Z type transformer |
Applicable transformer: | All kinds of transformers including Z type transformers |
Reference standards: | IEC76-1 and IEC60044 |
Ratio measurement range: | 1-10000 |
Group measurement: | 1-12 |
Size: | 325mm×278mm×188 mm |
Weight: | 7kg |
Power supply: | AC220V ± 10%, 50Hz/60Hz |
Warranty: | One year |
Service: | OEM service is available |
Company Info. |
Delta Technology (Chongqing) Co., Ltd. |
Verified Supplier |
View Contact Details |
Product List |
TTR-Z Transformer Turns Ratio Testing Equipment is specially designed for three-phase transformer in power system, especially for transformer of type Z winding and other transformers whose zero-load current is relatively high.
TTR-Z Transformer Turns Ratio Testing Equipment has wide testing range, fast testing speed, favorable repeatability, flexible data processing, convenient connection, complete protection, easy learning and convenient operation.
Applicable to transformers connected in Z type.
Two output voltages are optional and applicable to transformer whose zero-load current is relatively high.
Have wide testing range and the highest transformation ratio may reach 10000.
Automatically calculate tap position.
Fast speed, which is only 18 seconds for three-phase.
Favorable repeatability.
Automatically save 99 data at most.
Flexible data processing, including retrieval, print, transfer to U-disk, delete and upload to PC computer for testing.
Have transformer short-circuit protection and interturn short-circuit protection functions. In case of short circuit, relevant information will be displayed on the LCD screen in characters.
The upper computer could control the whole testing process, save data.
No. | Item Name | TTR-Z Z Type Transformer Turns Ratio Testing Equipment |
1 | Ratio measurement range | 1-10000 |
2 | Group measurement | 1-12 |
3 | Phase measurement error | 1 degree |
4 | Ratio measurement error | 1-2000 ± 0.2%RDG 2000-10000 ± 0.5%RDG |
5 | Test voltage | AC 0~80V continuously, frequency 50Hz |
6 | Power supply | AC220V ± 10%, 50Hz/60Hz |
7 | Environment temperature | 0-50°C |
8 | Humidity | ≤85%RH |
9 | Size | 325mm*278mm*188 mm |
10 | Weight | 7kg |
11 | Length of test cables | 8 meters |
![]() |