Sign In | Join Free | My xuijs.com |
|
Categories | Intelligent Temperature Controller |
---|---|
Brand Name: | Toky |
Model Number: | AI108 series |
Certification: | CE |
Place of Origin: | China |
MOQ: | 5sets |
Payment Terms: | T/T |
Delivery Time: | 15~35days |
Packaging Details: | Carton |
Usage: | Industrial |
Accuracy: | 0.5%FS |
Working voltage: | 100~240V AC/DC |
Power consumption: | ≤6W |
Working environment: | 0~50℃ <85%RH |
Relay output: | 3A/250V AC |
Company Info. |
Light Country(Changshu) Co.,Ltd |
Verified Supplier |
View Contact Details |
Product List |
AI108 Series Intelligent Temperature Controller 0.5%FS LED Display one loop output Alarm Heating/cooling controll
1. Features and advantages of AI108 digital temperature controller:
a). Easy operation,economic model.
b). 0.5%FS high-accuracy signal measurement.
c). 2 degree PID arithmetic, have self-tuning fuction.
d). Calculate the best control state automatically.
e). 1 loop alarm function with free setting.
f). Applied to heating control, cooling control, heating-cooling control. Widely used in the heating and cooling control in extruder.
2. Model specification:
3. Technical specification:
Parameter:
Sample rate | 2 times/per second |
Relay capacity | AC 250V /3A life of rated load> 100,00 times |
Power supply | AC/DC 100 ~ 240V ( 85-265V ) |
Power consumption | <6VA |
Environment | Temperature of indoor:0 ~ 50°C no condensation; Humidity : < 85%RH,altitude<2000m |
Storage environment | -10 ~ 60°C,no condersation |
SSR output | DC 24V pulse voltage,load<30mA |
Insulation impednce | in put,output, power VS meter cover > 20MQ |
ESD | IEC/EN61000-4-2 Contact ±4KV/Air ±8KV perf.Criteria B |
Pulse traip anti-interference | IEC/EN61000-4-4 ±2KV perf.Criteria B |
Surge immunity | IEC/EN61000-4-5 ±2KV perf.Criteria B |
Voltage frop & Short interruption immunity | IEC/EN61000-4-29 0% ~ 70% perf.Criteria B |
Dielectric strength | Signal input & output & power 1500SC1 min.below 60V low voltage DC500V,1min |
Total weight | About 400g |
Shell material | The shell and panel framePC/ABS (Flame class UL94V-0) |
panel material | PET(F150/F200) |
Power failure memory | 10years,times of writing:! million times |
Panel protection level | IP65(IEC60529) |
Safety standard | IEC61010-1 overvoltage categoryH,pollution level 2,level 11( Enhanced insulation ) |
Specification of measuring signal table:
4. Dimension:
5. Connections:
6. Contact:
Sales: bassy shi
Cell phone: +86 13773069136